6 the nec requires at least of free conductor in electrical device boxes for connection to switches and receptacles.
Type nm cable must be supported within.
Nm cable must be supported and secured every 4 ft.
Section 1201 2 of the icc ec 2001 supplement modifies the nec 1999 provisions to allow type nm cable in 4 story apartment buildings.
Nm b is what you will see when shopping for nm cable which is rated for 90 degrees c 194 degrees f.
Although in article 314 17 c s exception nonmetallic boxes have no cable clamps and must have cables supported within eight inches of the junction box.
Runs of nm cable must be supported at least every 54 inches.
Type mc cable of sizes 14 12 and 10 awg must be secured within 12 from every box and then must be supported at intervals not exceeding.
Type nm cable may not be used in any building of four or more stories.
Nonmetallic sheathed cable shall be supported and secured by staples cable ties straps hangers or similar fittings designed and installed so as not to damage the cable at intervals not exceeding 1 4 m 4 ft and within 300 mm 12 in of every outlet box junction box cabinet or fitting.
The nm cable must be supported within not more than 4 feet of the fixture according to 334 30 b.
Keep in mind that support does not always mean fastening the cable to framing.
General cable support.
The most common type of nm used are 2 wire and 3 wire.
And within 12 inches of every outlet box junction box cabinet or fitting.
314 17 c states that cables must be secured to the receptacle box.
There are many different ways to wire a dwelling during initial construction using nm cable.
However if this accessible ceiling is an occupancy other than one and two family and multifamily dwellings 334 12 a 2 does not permit the use of exposed type nm cable.
When nonmetallic device boxes that are 2 gang or more are used the installed type nm cable must be supported no more than inches from the box 12 when using aluminum conductors size conductor must be used to carry the same amount of current as a copper conductor.
When used as a branch circuit or feeder type se cable must be supported and secured in accordance with 334 30 at intervals not exceeding 4 feet and within 1 foot of every outlet box junction box cabinet or fitting.
Nm is normally used in one and two family dwellings and certain multifamily dwellings.
Section 338 10 b permits type se cable as branch circuits or feeders and contains multiple installation requirements.
Type nm cable in all buildings 3 stories or less prohibits type nm cable in buildings of 4 or more stories.